ICO 51 is a programmable digital panel meter 72 x 24 mm for electrical measurements in 10,000 points. It allows DC and AC voltage to be measured up to 400 V (true effective value with or without component continuous health) and DC and AC current to be measured up to 5 A using a small shunt screwed on the back connector.
- Panel meter size: 72 mm x 24 mm
- IP65 protected
- Measurement, display and scaling of:
- DC and AC voltage up to 400 V
- DC current up to 2,000 A with an external shunt
- AC current up to 200 A + Current transformer, with secondary current of 1 A or 5 A
- Frequency up to 5,000 Hz
- 9 different power supplies available
Electrical measurement indicator
Type | Range | Resolution | Accuracy (1 year) (23°C ± 1°C) |
Input impedance |
DC voltage | 500 mV 5 V 50 V 400 V |
100 μV 1 mV 10 mV 100 mV |
0.1% + 100 μV 0.1% + 1 mV 0.1% + 10 mV 0.1% + 0.1 V |
> 100 MΩ 1.1 MΩ 1 MΩ 1 MΩ |
AC voltage | 500 mV 5 V 50 V 400 V |
100 μV 1 mV 10 mV 100 mV |
0.7% + 1 mV 0.5% + 6 mV 0.5% + 60 mV 0.5% + 0.6 V |
1 MΩ 1 MΩ 1 MΩ 1 MΩ |
DC current | 4-20 mA or 0-50 mA 1 A (2) 5 A (2) |
10 µA 1 mA 1 mA |
0.2% + 10 µA |
shunt 10 W included |
AC current | 1 A (2) 5 A (2) |
1 mA |
external shunt 100 mV external shunt 100 mV |
Temperature coefficient: ≤ 10% accuracy/°C
Continuous mode: -40 to 100 % range.
Alternate mode: 4 to 100 % range from 25 to 500 Hz without D.C component (possible measurements up to 10 kHz on some ranges with less precision).
(1) Extended measurement range: -40 to +110% range.
(2) With external shunts
Common rejection mode: ³ 110 dB at 50 Hz on 500 mV DC range
Acceptable maximum voltage on voltage range: 600 V.
Acceptable maximum voltage: 250 V~ in common mode.
Automatic ranging
Further features
Measurement hold | Short-circuit on the rear panel |
Scaling | The value is to be entered using keyboard, while the value of measurement corresponding can be is introduced of the same way, is measured by the instrument. This possibility is very interesting for error corrections on temperature ranges. |
Sampling rate | 2.5 samples / s |
General specifications
Size | 99 x 36 x 120 mm |
Weight | 300 g |
Display | From -1999 to 9999 with indication LED red,yellow or green,of 14 mm |
Supply | 230 V at ± 10% (50 to 60 Hz) Other power supplies available in option |
Environmental specifications
Reference range | 23°C ± 1°C (20 to 75 % w/o condensing) |
Operating reference range | 0 to 50°C (RH: 20 to 75 % w/o condensing) |
Limit operating range | -10°C to +50°C (RH: 10 to 80 % w/o condensing) |
Indice de protection | IP40 in ABS case IP65 in watertight metallic case |